5 models and types, Models and types, Table 3: model numbers and installation distances – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual
Page 21
TM 799200 Rev (C), January 2014
Models and Types
9
2.5
Models and Types
Series 700S offers 2 families of detected gases:
Models 701S, 702S and 703S used for methane, LPG and gases mixture
for most offshore and onshore applications.
Models 721S, 722S and 723S used for ethylene only.
Table 3 describes the installation distances for each of the Series 700S
models.
Table 3: Model Numbers and Installation Distances
Model
No.
Detector
Source
Min.
Installation
Distance
Max.
Installation
Distance
701S
XDSS-C-111XX
XSS-C-11X
13 ft. (4 m)
65 ft. (20 m)
702S
XDSS-C-112XX
XSS-C-11X
50 ft. (15 m)
230 ft. (70 m)
703S
XDSS-C-113XX
XSS-C-12X 165 ft. (50 m) 459 ft. (140m)
721S
XDSS-C-121XX
XSS-C-11X
13 ft. (4 m)
65 ft. (20 m)
722S
XDSS-C-122XX
XSS-C-11X
50 ft. (15 m)
230 ft. (70 m)
723S
XDSS-C-123XX
XSS-C-12X 165 ft. (50 m) 459 ft. (140m)
The 700S Series has 3 wiring options:
Option 1: Power, Alarm Relay, Fault Relays, 0-20mA
Option 2: Power, Alarm Relays, Fault Relays, Accessory Relay
Option 3: Power, Alarm Relay, RS-485, 0-20mA, RS-485 RTN (default)
Note: SIL2 covers only 0-20mA outputs.
The wiring option must be set at the factory; cannot be changed at
customer facility.