KROHNE BM 100A Handbook User Manual
Page 17

 
 
Handbook BM 100 A
17
2 Electrical
Connections
2.1 Insulation
rating
 
The gauge transmitter electrical insulation conforms to IEC 1010-1. Please note the information 
below concerning each rating category. 
 
Category 
 
Rating Comments
Power supply 
 
overvoltage category 
III 
 
The gauge does not have an integrated switch or circuit-
breakers. These elements must be installed in 
conformance to local regulations and EU Low Voltage 
Guidelines and to properly isolate the equipment when 
necessary. Note that this is not obligatory for instruments 
with 24 V power supply boards. 
 
4 to 6.3 A time lag fuses are recommended for external 
installation. 
 
Fuses must be installed on every electrical conductor for 
the system to conform to current regulations. 
Note that the active phase conductor, L, is protected by an 
internal fuse: the neutral conductor, N, is not. 
Output circuit
overvoltage category II Fuses are unnecessary.
Insulation 
 
contamination level 2 
 
The contamination level refers to the protection of internal 
elements of the signal converter. 
 
Rated IP 67 (equivalent to NEMA 6-6P) against ingress of 
water and other foreign bodies. 
 
Note that the gauge can operate in contamination level 4 
conditions if installed correctly. 
Protection
class 1
 
 
Galvanic isolation of terminals 
 
The gauge conforms to the following standard and E.U. Directive: 
 
Standard/Directive Description 
EN (IEC) 61010-1 
Safety requirements for electrical equipment for measurement, control and 
laboratory use (low tension) 
73/23/EEC
Council Directive of 19 February 1973 on the harmonisation of the laws of 
Member States relating to electrical equipment designed for use within 
certain voltage limits (low voltage) modified by Directive 93/68/EEC (art.13). 
 
The BM 100 A gauge outputs are galvanically isolated from the power supply and ground in 
accordance with the regulations given above. An external barrier is unnecessary. 
 
 