Operation – KROHNE BW 25 EN User Manual
Page 37
OPERATION
6
37
BW25
www.krohne.com
09/2010 - 4000432302 MA BW25 R05 en
1.5.1
Inactive
1.5.2
RESET
ERROR
YES - NO
2.1
4-20mA OUT
The analogue current output can be set to fixed values in 10
% increments from 4.00...20.00mA. This function has no
influence on the binary switching outputs.
Note
Note
Note
Note
This test function is switched off in multi-drop mode.
Display: "NOT AVAILABLE".
2.2
OUTPUT B1
OPEN
The function assignment in menu 3.2 is not taken into
consideration here.
CLOSED
2.3
OUTPUT B2
OPEN
The function assignment in menu 3.2 is not taken into
consideration here.
CLOSED
2.4
Inactive
3.1
LANGUAGE
ENGLISH
DEUTSCH
FRANCAIS
ITALIANO
ESPANOL
CESKY
POLSKI
NEDERLANDS
3.2
FUNCTION B1
INACTIVE
Output B1 is switched off.
SWITCHING
POINT
The output B1 switches at a set value depending on the
current level value.
3.3
CONTACT B1
NC contact
Output B1 is normally closed. If an alarm situation occurs,
the contact opens.
NO CONTACT
Output B1 is normally open. If an alarm situation occurs,
the contact closes.
3.4
FUNCTION B2
INACTIVE
See FUNCTION B1
SWITCHING
POINT
See FUNCTION B1
3.5
CONTACT B2
NC contact
See CONTACT B1
NO CONTACT
See CONTACT B1
3.6
Inactive
3.7
Inactive
3.8
Inactive
3.9
MULTIDROP
0…15
Multi-drop mode means that the device is continuously
working in bus mode via HART
®
communication (max. 15
parallel devices). The analogue current output is then fixed
to 4.1 mA. Measured values are transmitted via HART
®
communication. However, the display allows local reading
of the measured values. The polling address can be set to 1
.... 15. Larger whole numbers are not permitted. If the
polling address is set to 0, HART
®
bus mode is switched off.
The device functions as analogue. The current output of 4-
20mA is active. Standard HART
®
communication is further
guaranteed.