Load for HART

®

communication

The maximum load resistance is calculated as follows:

Configuration

The electronic M10 indicator can be configured using HART

®

communication. DD (Device

Description) for AMS 6.x and PDM 5.2 as well as a DTM (Device Type Manager) are available for
configuration (go to download centre at www.krohne.com).

The current level can be transmitted using the integral HART

®

communications. Two limit values

can be monitored.

INFORMATION!
The power supply has to be able to supply a minimum of 22 mA.

INFORMATION!
For HART

®

communication a load of at least 230 ohm is required.

DANGER!
Use a twisted two-core cable to prevent electrical interference from impeding the DC output
signal.
In some cases a shielded cable may be necessary. The cable shield may only be earthed
(grounded) at one place (on the power supply unit).