beautypg.com

Operation, 3 calibration – KROHNE OPTISENS PAS 2000 EN User Manual

Page 24

background image

5

OPERATION

24

OPTISENS PAS 2000

www.krohne.com

11/2008 • MA PAS 2000 R04 en

Menu "Cleaning"

Menu "Scale / Alarm"

Menu "System"

5.3 Calibration

The sensor is shipped pre-calibrated, but since all electrodes are different, the sensor must be
calibrated with its electrode to give a good measurement. The electrode degrades by time and
calibrations shall be done regularly following a maintenance schedule.

Submenu

Description

Press ^ to go to the cleaning program

Cleaner

Cleaner

Cleaner

Cleaner

"None", "Flush" or "Brush". Do not select "Brush" since this does not exist for this
sensor.

Interval min

Interval min

Interval min

Interval min

0...999 minutes, time between cleaning cycles.

Length sec

Length sec

Length sec

Length sec

0...999 seconds, duration of flushing cycle.

Freeze sec

Freeze sec

Freeze sec

Freeze sec

0...999 seconds, extra freeze time of output signal after a flushing cycle.

Relay

Relay

Relay

Relay

"-", "1", "2", "Along 1" or "Along 2". Select relay to operate solenoid for flush cycle if
this sensor is a master with its own relay, or relay used by master if this sensor is a
slave. These are the same relays used for "Alarm relay"

"Alarm relay"

"Alarm relay"

"Alarm relay" below.

Next time

Next time

Next time

Next time

The next scheduled cleaning time. Pushing ^ on this line will set the time to current
time and start a cleaning cycle. This could be used to test the "Flush" cycle.

Submenu

Description

Max

Max

Max

Max

Measured value corresponding to 100 %, equal to 20 mA output signal (or 4 mA if 20-
4 mA is used).

Min

Min

Min

Min

Measured value corresponding to 0 %, equal to 4 mA output signal (or 20 mA if 20-4 mA
is used).

Hi-Alarm

Hi-Alarm

Hi-Alarm

Hi-Alarm

Level that activates an alarm when exceeded, 0 = not in use.

Low-Alarm

Low-Alarm

Low-Alarm

Low-Alarm

Level that activates an alarm when underpassed, 0 = not in use.

Alarm Relay

Alarm Relay

Alarm Relay

Alarm Relay

"-", "1", "2" or ”1 and 2”. Check that the relay is not being used for cleaning.

Submenu

Description

Type

Type

Type

Type

Type of sensor, read only.

Serial

Serial

Serial

Serial

Serial number of the sensor, read only.

SoftW

SoftW

SoftW

SoftW

Software version of the sensor, read only.

Press ^ to go to "info" read only menu. This menu is for KROHNE internal use.

Info

Info

Info

Info

RV 0 mV

Raw value for 0 mV.

RV 1000 mV

Raw value for 1000 mV.

Ch1

Raw value.

ORP mV

Current reading in millivolt.

Samp/s

Number of samples per second.

Service

Service

Service

Service

Not accessible for users.

.book Page 24 Friday, November 28, 2008 2:32 PM