Electrical connections, 10 interface cable, 11 grounding – KROHNE TIDALFLUX 4300 F EN User Manual
Page 25
ELECTRICAL CONNECTIONS
4
25
TIDALFLUX 4300 F
www.krohne.com
06/2010 - 4000970001 - TIDALFLUX 4300 F R01 en
4.10 Interface cable
The data interface cable is a shielded, 3 x 1.5 mm
2
Liycy cable. Standard is 10 m included in the
delivery. Connect the shielding at both sides of the cable via the special cable gland.
4.11 Grounding
Connecting shielding via special cable gland
Figure 4-11: Connecting the shield within the cable gland
1 Wires
2 Isolation
3 Shielding
4 Isolation
5 Feed cable through dome nut and clamping insert and fold shielding over clamping insert. Make sure that the braided
shield overlaps the O-ring by 2 mm / 3/32".
6 Push clamping insert into body.
7 Tighten the dome nut.
DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.
CAUTION!
In order to get a reliable height measurement it is absolutely necessary
absolutely necessary
absolutely necessary
absolutely necessary that the inner side of the
connecting pipeline is electrically conductive and connected to ground. If not, tailor-made
grounding rings with a cylindrical part can be delivered. Please contact your local agency in case
of doubt.