TECHNICAL DATA

7

43

TT 51 SERIES

www.krohne.com

09/2010 - 4000754201 - MA TT 51 R01 en

Input - thermocouples

Input - thermocouples

Input - thermocouples

Input - thermocouples

T/C type B - Pt30Rh-Pt6Rh (IEC 60584)

+400...+1800°C / +752...+3272°F

T/C type C - W5Re-W26Re (ASTM E 988)

0...+2315°C / +32...+4199°F

T/C type D - W3Re-W25Re (ASTM E 988)

T/C type E - NiCr-CuNi (IEC 60584)

-200...+1000°C / -328...+1832°F

T/C type J - Fe-CuNi (IEC 60584)

T/C type K - NiCr-NiAl (IEC 60584)

-200...+1350°C / -328...+2462°F

T/C type N - NiCrSi-NiSiMg (IEC 60584)

-100...+1300°C / -148...+2372°F

T/C type R - Pt13Rh-Pt (IEC 60584)

-50...+1750°C / -58...+3182°F

T/C type S - Pt10Rh-Pt (IEC 60584)

T/C type T - Cu-CuNi (IEC 60584)

-200...+400°C / -328...+752°F

Input impedance

>10 MΩ

Maximum wire loop resistance

10000 Ω (including T/C sensor)

Cold Junction Compensation (CJC)

Internal, external (Pt100) or fixed

Input - voltage

Input - voltage

Input - voltage

Input - voltage

Range

-10...+1000 mV

Minimum span

2 mV

Customized linearization

Up to 50 points

Input impedance

>10 MΩ

Maximum wire loop resistance

500 Ω

Double inputs for RTD and thermocouple

Double inputs for RTD and thermocouple

Double inputs for RTD and thermocouple

Double inputs for RTD and thermocouple

Measure mode

Single temperature: T1 or T2

Differential temperature: T1 - T2 or T2 - T1

Average temperature: 0.5 x (T1 + T2)

Minimum temperature: lowest of T1 and T2

Maximum temperature: highest of T1 and T2

Sensor backup

Single or average mode: failure on one sensor activates automatic

switchover to the other sensor

Sensor drift monitoring

Single or average mode: adjustable acceptance level of the differential

temperature of sensor 1 and 2