Input - thermocouples
Input - thermocouples
Input - thermocouples
Input - thermocouples
T/C type B - Pt30Rh-Pt6Rh (IEC 60584)
+400...+1800°C / +752...+3272°F
T/C type C - W5Re-W26Re (ASTM E 988)
0...+2315°C / +32...+4199°F
T/C type D - W3Re-W25Re (ASTM E 988)
T/C type E - NiCr-CuNi (IEC 60584)
-200...+1000°C / -328...+1832°F
T/C type J - Fe-CuNi (IEC 60584)
T/C type K - NiCr-NiAl (IEC 60584)
-200...+1350°C / -328...+2462°F
T/C type N - NiCrSi-NiSiMg (IEC 60584)
-100...+1300°C / -148...+2372°F
T/C type R - Pt13Rh-Pt (IEC 60584)
-50...+1750°C / -58...+3182°F
T/C type S - Pt10Rh-Pt (IEC 60584)
T/C type T - Cu-CuNi (IEC 60584)
-200...+400°C / -328...+752°F
Input impedance
>10 MΩ
Maximum wire loop resistance
10000 Ω (including T/C sensor)
Cold Junction Compensation (CJC)
Internal, external (Pt100) or fixed
Input - voltage
Input - voltage
Input - voltage
Input - voltage
Range
-10...+1000 mV
Minimum span
2 mV
Customized linearization
Up to 50 points
Input impedance
>10 MΩ
Maximum wire loop resistance
500 Ω
Double inputs for RTD and thermocouple
Double inputs for RTD and thermocouple
Double inputs for RTD and thermocouple
Double inputs for RTD and thermocouple
Measure mode
Single temperature: T1 or T2
Differential temperature: T1 - T2 or T2 - T1
Average temperature: 0.5 x (T1 + T2)
Minimum temperature: lowest of T1 and T2
Maximum temperature: highest of T1 and T2
Sensor backup
Single or average mode: failure on one sensor activates automatic
switchover to the other sensor
Sensor drift monitoring
Single or average mode: adjustable acceptance level of the differential
temperature of sensor 1 and 2