Operation, 2 factory settings for configuration – KROHNE OPTITEMP TT 51 EN User Manual

Page 27

background image

OPERATION

5

27

TT 51 SERIES

www.krohne.com

09/2010 - 4000754201 - MA TT 51 R01 en

5.2 Factory settings for configuration

The transmitters are delivered with either a factory settings or configured according to
customers' specifications.

DANGER!
Only an Ex approved HART

®

modem located in safe area may be connected to a transmitter

placed in potentially explosive area.

Menu

Designation

Parameter

Factory settings

Device Root menu

-> Sensors

-> -> Channel 1

Type of sensor 1

RTD Pt100 α=0.003850

Number of wires

4

PV Lower range value

0

PV Upper range value

100

Digital units

°

C

Lock code

Unlocked

Damping value

4 s

Line frequency

55 Hz

Isolation resistance monitoring

Off

Sensor break (Off/Down scale/Up scale)

Upscale

Sensor short circuit (Off/Down scale/Up scale)

Upscale

Sensor drift (Off/Down scale/Up scale)

Off

-> -> Channel 2

Type of sensor 2

None

Number of wires

PV Lower range value

PV Upper range value

Digital units

°

C

Lock code

Unlocked

Damping value

4 s

Line frequency

55 Hz

Isolation resistance monitoring

Off

Sensor break (Off/Down scale/Up scale)

Off

Sensor short circuit (Off/Down scale/Up scale)

Off

Sensor drift (Off/Down scale/Up scale)

Off