Operation, 2 factory settings for configuration – KROHNE OPTITEMP TT 51 EN User Manual
Page 27
OPERATION
5
27
TT 51 SERIES
www.krohne.com
09/2010 - 4000754201 - MA TT 51 R01 en
5.2 Factory settings for configuration
The transmitters are delivered with either a factory settings or configured according to
customers' specifications.
DANGER!
Only an Ex approved HART
®
modem located in safe area may be connected to a transmitter
placed in potentially explosive area.
Menu
Designation
Parameter
Factory settings
Device Root menu
-> Sensors
-> -> Channel 1
Type of sensor 1
RTD Pt100 α=0.003850
Number of wires
4
PV Lower range value
0
PV Upper range value
100
Digital units
°
C
Lock code
Unlocked
Damping value
4 s
Line frequency
55 Hz
Isolation resistance monitoring
Off
Sensor break (Off/Down scale/Up scale)
Upscale
Sensor short circuit (Off/Down scale/Up scale)
Upscale
Sensor drift (Off/Down scale/Up scale)
Off
-> -> Channel 2
Type of sensor 2
None
Number of wires
PV Lower range value
PV Upper range value
Digital units
°
C
Lock code
Unlocked
Damping value
4 s
Line frequency
55 Hz
Isolation resistance monitoring
Off
Sensor break (Off/Down scale/Up scale)
Off
Sensor short circuit (Off/Down scale/Up scale)
Off
Sensor drift (Off/Down scale/Up scale)
Off