beautypg.com

Electrical connections – KROHNE OPTITEMP TT 51 EN User Manual

Page 18

background image

4

ELECTRICAL CONNECTIONS

18

TT 51 SERIES

www.krohne.com

09/2010 - 4000754201 - MA TT 51 R01 en

4.4 Connection diagram of in-head transmitter (intrinsically safe)

Figure 4-2: Connection diagram

1 Input
2 Potentially explosive area
3 Safe area
4 Modem, Ex-approved
5 Modem
6 R

Load

, R ≥ 250 Ω

7 Zener barrier or voltage supply 10…30 VDC (intrinsically safe)
8 Output
9 See chapter "cable length"

INFORMATION!
The HART

®

modem is connected parallel to the output load or parallel to the output of the

transmitter.

DANGER!
The transmitter may be operated in areas with potentially explosive atmospheres if the voltage
supply is ensured by means of an appropriate power supply unit or a Zener barrier!
In potentially explosive areas only Ex approved HART

®

modems may be used. The safety

instructions for operation in potentially explosive areas must be observed.
In order to ensure reliable HART

®

communication with this transmitter, the maximum cable

length of the output circuit must be observed. For detailed information refer to Cable length on
page 23

.