Messages in AMS, PDM and FC375 device diagnostic Actions

Device specific

Failure Error message

Error correction

Transmitter

F

Sensor break channel 1

Sensor wire broken. Check the sensor and sensor

connection on the channel 1. If error remains replace the

sensor connected to channel 1.

Transmitter

F

Sensor break channel 2

Sensor wire broken. Check the sensor and sensor

connection on the channel 2. If error remains replace the

sensor connected to channel 2.

Transmitter

F

Sensor short circuit

channel 1

Sensor wire shorted. Check the sensor and sensor

connection on the channel 1. If error remains replace the

sensor connected to channel 1.

Transmitter

F

Sensor short circuit

channel 2

Sensor wire shorted. Check the sensor and sensor

connection on the channel 2. If error remains replace the

sensor connected to channel 2.

Transmitter

F

Sensor low isolation

channel 1

To low isolation in the sensor. Check the sensor by

measuring resistance between the wires. If error remains

replace the sensor connected to channel 1.

Transmitter

F

Sensor low isolation

channel 2

To low isolation in the sensor. Check the sensor by

measuring resistance between the wires. If error remains

replace the sensor connected to channel 2.

Transmitter

F

Sensor drift

Check the sensors and limits for sensor drift. If error

remains replace the faulty sensor.

Transmitter

F

System error

Make a self test to find out more. If the error remains

replace the device.

Messages in AMS, PDM and FC375 device diagnostic Actions

Device specific

Out of
specifi-
cation

Error message

Error correction

Transmitter

S

High limit alarm OPM

Check the sensor(s) and sensor connection on both

channels. If error remains replace the sensor(s)

connected to the transmitter.

Transmitter

S

Low limit alarm OPM

Check the sensor(s) and sensor connection on both

channels. If error remains replace the sensor(s)

connected to the transmitter.

Messages in AMS, PDM and FC375 device diagnostic Actions

Device specific

Mainte-

nance

required

Error message

Error correction

Transmitter

M

Sensor backup

Transmitter is measuring the working sensor (channel).

Replace the faulty sensor.