OPERATION

5

35

TT 51 SERIES

www.krohne.com

09/2010 - 4000754201 - MA TT 51 R01 en

5.6 Factory calibration of transmitter

The transmitters are delivered with a factory configuration Pt100 (α=0.00385), 4-wire connection
0...+100°C / +32...+212°F or configured according to customer's requirements. For detailed
information refer to

Factory settings for configuration

on page 27.

Due to the long-term drift of max. ±0.01°C or ±0.01% of span per year, a re-calibration of the
transmitter is normally not needed. Should you for any reason require the re-calibration, the
transmitter must be returned to the factory.