OPERATION

5

31

TT 51 SERIES

www.krohne.com

09/2010 - 4000754201 - MA TT 51 R01 en

5.3.2 Configuration with a hand held communicator FC375/FC475

The Field communicators FC375/FC475 are hand held communicators from Emerson Process
Management for configuring HART

®

and Foundation Fieldbus devices. To be able to configure

the transmitter with the FC375/FC475 you need a Device Description (DD) file.

The transmitter DD has to be installed on the FC375/FC475, otherwise the user will work with
the transmitter as generic device loosing opportunity to control all features of the transmitter.
For installing DD on the FC375/FC475 the "Easy Upgrade Programming Utility" is needed and the
FC375/FC475 must have a system card with "Easy Upgrade" option (see details in the "375/475
Field Communicator User’s Manual").

The transmitter DD for FC375/FC475 can also be downloaded from our website. For information
about installing, follow the instructions in the attached "readme.txt" file.

For proper connection of transmitter with the hand held communicator refer to

Connection

diagram of in-head transmitter (non-incendive)

on page 17 and refer to

Connection diagram of

rail-mount transmitter (non-incendive)

on page 22.

To configure the transmitter for areas with potentially explosive atmospheres refer to

Connection diagram of in-head transmitter (intrinsically safe)

on page 18 and refer to

Connection diagram of rail-mount transmitter (intrinsically safe)

on page 23.

5.3.3 Device management software

The transmitter can be configured via the PC software as AMS (Asset Management System) and
Simatic PDM.

Asset Management Solutions Device Manager (AMS)

Asset Management Solutions Device Manager (AMS)

Asset Management Solutions Device Manager (AMS)

Asset Management Solutions Device Manager (AMS)

The AMS is a PC application from Emerson Process Management for configuring and managing
HART

®

and Foundation Fieldbus devices. For adaptation to different devices AMS uses Device

Descriptions (DD).

The transmitter DD has to be installed on the AMS system and a so called "Installation Kit HART
AMS" is needed (available as download on the internet). For installing the DD with the
installation kit refer to the "AMS Intelligent Device Manager Books Online" section "Basic AMS
Functionality /Device Configurations / Installing Device Types / Procedures /Install device types
from media". Please read also the "readme.txt", which is also contained in the installation kit.

The transmitter DD for AMS can also be downloaded from our website. For information about
installing, follow the instructions in the attached "readme.txt" file.

AMS supports the "EDDL Process Variables Root Menu", the "Diagnostic Root Menu" and the
"Device Root Menu" for online access to the device.