Input - voltage

Input - voltage

Input - voltage

Input - voltage

Range

-10...+500 mV

Minimum span

2 mV

Customized linearization

Up to 50 points

Input impedance

>10 MΩ

Maximum wire loop resistance

500 Ω

Output

Output

Output

Output

Output signal

4...20 mA, 20...4 mA or customized

Temperature linear for RTD & T/C

HART

®

protocol

HART

®

5

Adjustable output filtering

0...10 s (time constant)

Permissible load

Note: Communication according to HART

®

always requires a resistance

greater than 250 Ω! For TT 50 C Ex and TT 50 R a greater load than the

below-mentioned is allowed with a higher supply voltage, see output load

diagram.

TT 50 C: 610 Ω at 24 VDC and 23 mA

TT 50 C Ex: 520 Ω at 24 VDC and 23 mA

TT 50 R: 565 Ω at 24 VDC and 23 mA.

Configuration

Configuration

Configuration

Configuration

HartSoft

The PC configuration software "HartSoft" is a versatile and user-friendly tool

for transmitter configuration, loop check-up and sensor diagnostics. It runs

on Windows 2000, XP and Vista.

Alternatives

Hand held communicator, e.g. FC375/FC475 (Emerson)

Management systems, e.g. AMS (Emerson) and PDM (Siemens)

EDD enabled systems

Approvals and certifications

CE

The device fulfils the statutory requirements of the EC directives.

The manufacturer certifies that these requirements have been met by

applying the CE marking.

Intrinsically safe version

ATEX: II 1 G Ex ia IIC T4/T5/T6

Electromagnetic compatibility

Directive: 2004/108/EC.

Harmonized standards: EN 61326-1:2006.

.book Page 33 Monday, September 13, 2010 5:07 PM