5.1.2 Multi-drop connection (2-wire connection)

As a multipoint connection (Multidrop) with up to 15 devices in parallel (this transmitter or other
HART

®

devices).

The current outputs of the devices must be passive!

Burst mode is not supported.

1 Primary master
2 HART

®

modem

3 HART

®

signal

4 Other HART

®

devices or this transmitter (refer also to 7)

5 Terminal 5
6 Terminal 6
7 Device with address > 0 and passive current output, connection of max. 15 devices (slaves)
8 Secondary Master
9 Power supply for devices (slaves) with passive current output
10 Load ≥ 250 Ω (Ohm)