To calculate the maximum cable length for the output circuit, determine the total resistance of
the output loop (load resistance + approximate cable resistance). Find out the capacitance of the
cable being used. In the following tables you can find the maximum cable length based on the
typical values for 1 mm

2

cables. CN is the abbreviation for "Capacitance Number" which is

multiple of 5000 pF present in the device.

For multiple connections (multidrop mode), the following formula shall be used:

L = [(65 x 10

6

) / (R x C)] x (Cn x 5000 + 10000) / C

with
L: cable length [m or ft]
R: load resistance (incl. the resistance of any Zener barrier) + cable resistsance [Ω]
C: cable capacitance [pF/m or pF/ft]
Cn: number of transmitters in the loop

1 Cable length [m]
2 Cable length [ft]
3 Load resistance and cable resistance
4 200 pF per m/ft
5 150 pF per m/ft
6 100 pF per m/ft