TECHNICAL DATA

30

OPTITEMP TT 50 C/R

www.krohne.com

09/2010 - 4000636502 - MA OPTITEMP TT 50 C/R R03 en

7.2 Technical data

INFORMATION!

The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local representative.

Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).

Measuring system

Application range

Temperature, resistance or voltage measurements of solids, liquids and

gases in industrial environment.

Design

Versions

Versions

Versions

Versions

TT 50 C

In-head transmitter which is intended for installation in a "B connection

head" or larger according to DIN 43729.

This transmitter is optionally available in an intrinsically safe version for

installation in potentially explosive areas (TT 50 C Ex).

TT 50 R

Rail-mount transmitter which is intended for installation on a top-hat rail

according to DIN 50022 / EN 60715.

Features

Features

Features

Features

HART

®

5 compliance

The transmitter are fully compliant with the HART

®

5 protocol. HART

®

5

offers the possibility to receive diagnostic information such as sensor errors

or sensor conditions.

Sensor isolation monitoring

The isolation resistance of thermocouples and RTD’s as well as the cabling

between sensor and transmitter is being monitored. If the isolation is below

a user-defined level, this will be indicated in ConSoft and with a diagnostic
HART

®

message, and the output signal can be forced upscale or downscale.

This feature requires an extra lead inside the thermocouple or RTD.

Customized linearization

For resistance and mV inputs, the 50-point customized linearization can

provide a correct process value, in a choice of engineering units, for a sensor

with non-linear input/output relation.

Sensor break monitoring

User-definable output: 3.6...22.8 mA.

Measuring accuracy

Accuracy

RTD and thermocouple: for detailed information refer to

RTD and T/C

accuracy table on page 38.
Resistance: ±0.1 Ω or ±0.1% of span

Voltage: ±20 µV or ±0.1% of span

Temperature influence

RTD and thermocouple: for detailed information refer to

RTD and T/C

accuracy table on page 38.
Resistance: ±0.01% of span per °C or °F

Voltage: ±0.01% of span per °C or °F

.book Page 30 Monday, September 13, 2010 5:07 PM