Operation – KROHNE OPTIFLEX 2200 C_F Quickstart EN User Manual

Page 47

background image

OPERATION

4

47

OPTIFLEX 2200 C/F

www.krohne.com

08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en

[>>>>] to change Scale 4 mA.

[>>>>] to change the position of the cursor.

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

Use this step to give the 4 mA output

setting (0% limit) in the tank. Refer to the

illustrations that follow. Illustration 1

shows the settings for level. Illustration 2

shows the settings for distance.

[>>>>] to change Scale 20 mA.

[>>>>] to change the position of the cursor.

[

] to decrease the value or [

] to

increase the value.

[^

^

^

^] to confirm.

Use this step to give the 20 mA output

setting (100% limit) in the tank. Refer to

the illustrations that follow. Illustration 1

shows the settings for level. Illustration 2

shows the settings for distance.

[

] or [

] for the selection of the error

delay (0 s, 10 s, 20 s, 30 s, 1 mn, 2 mn,
5 mn or 15 mn).

[^

^

^

^] to confirm.

The time after which the current output

changes to an error value. The error value

shows that there is a measurement error.

[>>>>] to change the tag name.

[>>>>] to change the position of the cursor.

[

] to decrease the alphanumeric value

(A, B, ..., 1, 2, ...) or [

] to increase the

alphanumeric value.

[^

^

^

^] to confirm.

2 × [^

^

^

^] to confirm.

[

] or [

] for the selection of the save

option (STORE NO or STORE YES).

[^

^

^

^] to confirm.

Set to STORE YES to save and use the data.

Set to STORE NO to cancel the changes to

the device settings.

Screen

Steps

Description