beautypg.com

Installation, 8 installation recommendations for liquids, 1 general requirements – KROHNE OPTIFLEX 2200 C_F Quickstart EN User Manual

Page 13

background image

INSTALLATION

2

13

OPTIFLEX 2200 C/F

www.krohne.com

08/2013 - 4000622103 - QS OPTIFLEX 2200 R03 en

2.8 Installation recommendations for liquids

2.8.1 General requirements

Clearance between the probe and other objects in the tank

Figure 2-14: Installation recommendations for liquids

1 The electromagnetic (EM) field generated by the device. It has a radius of R

min

. Make sure that the EM field is clear of

objects and product flow. Refer to the table that follows.

2 If there are too many objects in the tank, install a bypass chamber or stilling well.
3 Keep the probe straight. If the probe is too long, shorten the probe length. Make sure that the device is configured with

the new probe length. For more data on the procedure, refer to the handbook.

4 Empty space. Refer to the table that follows.

Probe type

Empty space (radius, R

min

), around the probe

[mm]

[inches]

Coaxial

0

0

Double rod / cable

100

4

Single rod / cable

300

12