Table 1. output ratings and specifications, Power rating vs. temperature and input voltage, Output ratings and specifications – KEPCO RKE 1500W Series Operator Manual User Manual

Page 5: E 1 co

background image

RKE 1500W 021913

3

FIGURE 3. POWER RATING VS. TEMPERATURE AND INPUT VOLTAGE

TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS

MODEL RKE 1500W

24-50K

36-42K

48-32K

Output Volts d-c

24V

36V

48V

Adjustment Range (Volts d-c)

16.8-31.2

25.2-55.0

33.6-55.0

Voltage Setting (Volts d-c)

24 ±0.48

36 ±0.48

48 ±0.48

Maximum Output Ratings

(1)

(A,W)

85-90V a-c Input:

30-35A/720-840W

N/A

16-19.2A/(768-922W)

85-95V a-c Input:

N/A

21-25.2A/756-907W

N/A

90-170V a-c Input:

35A/840W

N/A

N/A

95-170V a-c Input:

N/A

25.2A/907W

19.2A/922W

170-265V a-c Input:

50A/1200W

42A/1512A

32A/1536W

Current Limit Setting
(Amps)

(2)

85 - 90V a-c input

31-57.5

(3)

22.3-48.3

(3)

17-36.8

(3)

90 - 170V a-c input

36-57.5

(3)

26-48.3

(3)

20-36.8

(3)

170 - 265V a-c input

52.5-57.5

(4)

44.1-48.3

(4)

33.6-36.8

(4)

Overcurrent Setting (Amps(

55-65

N/A

33.6-36.8

Current Short Circuit (Amps)

70

N/A

45

OVP Setting (Volts)

(5)

32-35

56-60

56-60

Low Output Voltage Protection Setting

14.4V(

≤60% V

Onom

)

≤5V

28.8V (

≤60% V

Onom

)

Efficiency% typical

AC Input 100V

83

81

85

AC Input 200V

85

86

88

Ripple & Noise

(6)

(mV, p-p)

ripple

200

300

300

ripple noise

300

400

400

(1)

See Figure 3 for power derating vs temperature and input voltage.

(2)

Current limit value determined by the combination of input voltage and output voltage setting. For example, if RKE 48-23K is
operated at 120V a-c and output voltage is set at the minimum of output range (33.6V), current limit is closer to the maximum
specified value of 36.8A. For the same input voltage (120Vac) if output voltage is set at maximum (55.0V), then the current
limit value is closer to 20A (the minimum current limit value specified for input voltage range 90-170V a-c).

(3)

Winker (intermittent) Operation; after cause is removed, output voltage restored automatically, however for some combina-
tions of input voltage and output voltage and current limit characteristics may be square type: see note (4) below.

(4)

Square type. Unit first enters Current Limit; output voltage starts to drop (nearly square curve). If cause is removed while in
Current Limit, output voltage restores automatically. If current continues to increase, Overcurrent is triggered. If Overcurrent
is combined with an output voltage drop below 60% of rated output voltage (below 5V for 36V model), the unit shuts OFF;
recovery is by removing, then reapplying input power after approximately 30 seconds or by opening and (without waiting)
reclosing the RC terminals.

(5)

When overvoltage is detected, output is shut OFF. Recovery is by removing, then reapplying input power after approximately
30 seconds or by opening and (without waiting) reclosing the RC terminals.

(6)

Ripple and noise levels above are satisfied when conditions are 0 to 100% load, 0 to 65°C (load is derated from 50 to 65°C,
see Figure 3), and bandwidth

≤100MHz.

36 V MODEL
48 V MODEL

24V MODEL

POWER RATING VS. INPUT VOLTAGE

POWER RATING VS. TEMPERATURE