beautypg.com

2 shield in full conduit, Shield in full conduit – Fire-Lite LCD-80FC Remote Fire Indicator User Manual

Page 21

background image

LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

21

Shield in Full Conduit

EIA-485 Shield Termination

5.2 Shield in Full Conduit

The EIA-485 line allows the FACP to communicate with the LCD-80FC Indicator. The shield for
the EIA-485 line must be connected to earth ground at the FACP (both exiting and entering the
FACP) but must be left floating (no connection) at the indicator if it is the first or only device on the
EIA-485 line. If a second indicator is connected, the shield leaving the first indicator must be float-
ing. The shield entering the second indicator must be connected to the Earth Ground terminal (P2-
7) on the second indicator. If additional indicators are connected, the shield leaving each indicator
must be left floating and the shield entering the following unit must be connected to the Earth
Ground terminal (P2-7) on the indicator.

!

CAUTION:

INSULATE FLOATING END

DO NOT ALLOW THE FLOATING SHIELD END (NO CONNECTION) TO CONTACT THE
CONDUIT. THE FLOATING END SHOULD BE INSULATED FROM EARTH GROUND.

LCD-80FC Box

LCD-80FC

P1-2 (+)
EIA-485 (IN)

P1-4 (-)
EIA-485 (IN)

P2-7 Earth
Ground (IN)

Connect the shield drain wire to the Earth

Ground Terminal on the Indicator

Shield Drain Wire

fd

u

8

0n

os

.w

mf

indicator

indicator

indicator

FACP

Figure 5.2 EIA-485 in Conduit

earth

ground

earth

ground

Shield

EIA-485 Loop

in conduit

NOTE:
1. Power-limited 24 VDC power may be run in the same conduit as the EIA-485 wiring.
2. Twisted, shielded wire is recommended for the EIA-485 communications loop.
3. Each electrical backbox is connected to earth ground via the conduit.
4. Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP.