5.0 Modbus™ Communications
The 1640 Controller features a Modbus compatible communications protocol and is addressable by a PLC,
PC/HMI, DCS, or other Modbus RTU master-polling devices. Communication is accomplished by two wire
half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, through the controller COM1 connection port
(P3). The Slave ID number is defaulted to 01Hex.
Modbus™ Register Detail:
Code 03 - Read Holding Registers, is the only code supported by the 1640.
Register #
40000
Channel 1 Reading
40001
Channel 2 Reading
40002
Channel 3 Reading
40003
Channel 4 Reading
40004
Channel 5 Reading
40005
Channel 6 Reading
40006
Channel 7 Reading
40007
Channel 8 Reading
40008
Channel 9 Reading
40009
Channel 10 Reading
4000A
Channel 11 Reading
4000B
Channel 12 Reading
4000C
Channel 13 Reading
4000D
Channel 14 Reading
4000E
Channel 15 Reading
4000F
Channel 16 Reading
40010
Channel 17 Reading
40011
Channel 18 Reading
40012
Channel 19 Reading
40013
Channel 20 Reading
40014
Channel 21 Reading
40015
Channel 22 Reading
40016
Channel 23 Reading
40017
Channel 24 Reading
40018
Channel 25 Reading
40019
Channel 26 Reading
4001A
Channel 27 Reading
4001B
Channel 28 Reading
4001C
Channel 29 Reading
4001D
Channel 30 Reading
4001E
Channel 31 Reading
4001F
Channel 32 Reading