1640-N4X

1640-N4X Instruction Manual

Rev. 0.0

Page 17 of 28

5.0 Modbus™ Communications



The 1640 Controller features a Modbus compatible communications protocol and is addressable by a PLC,
PC/HMI, DCS, or other Modbus RTU master-polling devices. Communication is accomplished by two wire
half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, through the controller COM1 connection port
(P3). The Slave ID number is defaulted to 01Hex.

Modbus™ Register Detail:
Code 03 - Read Holding Registers, is the only code supported by the 1640.

Register #
40000

Channel 1 Reading

40001

Channel 2 Reading

40002

Channel 3 Reading

40003

Channel 4 Reading

40004

Channel 5 Reading

40005

Channel 6 Reading

40006

Channel 7 Reading

40007

Channel 8 Reading

40008

Channel 9 Reading

40009

Channel 10 Reading

4000A

Channel 11 Reading

4000B

Channel 12 Reading

4000C

Channel 13 Reading

4000D

Channel 14 Reading

4000E

Channel 15 Reading

4000F

Channel 16 Reading

40010

Channel 17 Reading

40011

Channel 18 Reading

40012

Channel 19 Reading

40013

Channel 20 Reading

40014

Channel 21 Reading

40015

Channel 22 Reading

40016

Channel 23 Reading

40017

Channel 24 Reading

40018

Channel 25 Reading

40019

Channel 26 Reading

4001A

Channel 27 Reading

4001B

Channel 28 Reading

4001C

Channel 29 Reading

4001D

Channel 30 Reading

4001E

Channel 31 Reading

4001F

Channel 32 Reading