2.0 Unit Configuration


The Model 1640 is designed to monitor and display the status of up to 32 field sensor devices, provide power,
and programmable alarm outputs. The unit displays real time channel information on a 1” X 5” backlit LCD.
Display information includes the channel number, the gas type, and the gas concentration. The unit will also
display the current Alarm/Fault status via the front panel LED indicators.

The unit is equipped with a set of terminal blocks for A/C input, a set of terminal blocks for the connection of
the RS-485 Modbus™ and power to serial sensors, and a 5-pin plug for the connection of up to 8 Detcon DA4
Analog Sensor Modules that can be mounted inside the enclosure. Alarms are wire via 3-pin plugs directly to
the controller PCA.

2.1 Specifications


Capacity

User Configurable up to 32 devices, Analog and/or Serial


Input

RS-485 Modbus™ RTU (Analog Sensors communicate via the Detcon DA4 Modules)


Accuracy

±1% Full Scale Range


Outputs

User Configurable Relays:

4 relays (Fault, Alarm 1, Alarm 2, and Alarm 3)

Qty 4 Relays: 1 Form C Contacts per relay

Rated for 5A @ 30VDC, 5A @ 250VAC

RS-485 Modbus™ Slave


Power Input
100-240VAC

50~60Hz


Power Consumption

Base Unit <5W – Total Power is dependent on number of I/O modules, number of sensors, and the type

of sensors attached. Total power of the unit, with I/O modules and attached devices, not to exceed 200 Watts.

Display

1” X 5” Backlit LCD


Electrical Classification

NEMA 4X Enclosure


Dimensions

13.85''W x 15.75''H x 6.5''D


Operating Temperature Range

0°C to +45°C


Warranty
One

year