Figure 6 installation with 700 gas sensor, Figure 7 remote 700 gas sensor with hart-ram – Detcon 700 Series Remote Sensor/Alarm Relay Module With HART Interface User Manual

Page 8

background image

700 HART-RAM I.M.

The user will typically connect the 700 Gas Sensor directly to the HART-RAM if there is no requirement for
remote sensor separation (Figure 6). In this case, the 700 sensor will not require its own junction box and it
is not necessary to install/use the transient protection module shipped with the 700 sensor. The 700 sensor
may arrive from the factory pre-assembled with the HART-RAM in the j-box, but only if it is ordered in this
configuration. In this configuration, the wires from the 700 sensor will be directly connected to the 6-pin
terminal block labeled “SENSOR” on the terminal board.

NOTE: If the 700 sensor and HART-RAM are directly connected, it is not necessary to
install/use the transient protection module that is shipped with every 700 Gas Sensor.

Sensor

Power Input

mA/HART Output

Modbus

Interface

Fault

Annunciator

Alarm 1
Annunciator

Alarm 2
Annunciator

PGM2

SPAN

detcon inc.

MODEL
XX-700

PGM1

ZERO

Figure 6 Installation with 700 Gas Sensor


If remote sensor separation is required, the HART-RAM will be separated from the 700 sensor. Remote
separation distances of up to 1000 feet are possible with the recommended cables.

NOTE: It is highly recommended to install the interconnecting cabling inside rigid metal
conduit to eliminate potential EMI and RFI interference.

mA/HART Output

700 HART-RAM

Module

Cabling to/from Remote

700 Series Sensor

Remote 700

Series Sensor

Transient Protection

Module in Detcon

standard J-Box

Power Input

Sensor

detcon inc.

MODEL

XX-700

PGM1

ZERO

PGM2

SPAN

Modbus

Interface

Power & Modbus

Figure 7 Remote 700 Gas Sensor with HART-RAM

700 HART-RAM I.M.

Rev. 0.0

Page 4 of 24