Hart setup, Figure 16 hart setup – Detcon 700 Series Remote Sensor/Alarm Relay Module With HART Interface User Manual
Page 26
700 HART-RAM I.M.
Loop Test
1) Ensure that the DVM is connected as prescribed in Figure 15:
a) Disconnect the wire from the HART Connectors mA/HART position.
b) Connect one end of a 100~250Ohm resistor to the mA/HART position of the HART Connector.
c) Connect the positive lead of a DVM set to measure milliamps to the other end of the resistor.
d) Connect the negative lead (-) of the DVM to the GND position of the connector. (Figure 15)
2) Select “Loop test” from the Loop test Calibrate section of the screen.
3) The procedure will prompt for a setting (“4mA”, “20mA”, “Other”, and “End”).
4) Select one of the settings or “End” to exit.
5) If “Other” is selected, the procedure will prompt for a value. Only valid values will be accepted.
6) Select “OK”.
7) The HART-RAM will set the output for selected milliamp value.
8) Compare the reading on the DVM to the output displayed. Select “OK” when ready to continue
9) The procedure will return to Step 3. If “End” is selected, the HART-RAM will exit Loop test and return
to automatic control.
6.3.3 HART Setup
The HART Setup Screen allows parameters of the HART-RAM to be changed or modified. Changes made
on this screen will not be applied until power is cycled on the unit.
Figure 16 HART Setup
• Tag – Text that is associated with the field device installation. This text can be used by the user in
any way. A recommended use is a unique label that correlates to a field device label: a plant
drawing, or on a control system. This variable is also used as a type of data link layer address handle.
• Long Tag – Functions exactly like the Tag except the size is larger (max 32 ISO Latin 1 characters).
• Descriptor – Text that is associated with the field device. This text can be used by the user in any
way. There is no specific recommended use.
• Message – Text that is associated with the field device. This text can be used by the user in any way.
There is no specific recommended use.
700 HART-RAM I.M.
Rev. 0.0
Page 22 of 24