6 display settings, 7 about system, 0 warranty – Detcon SW-HMI-32-N7 User Manual
Page 22: Display settings, About system, Warranty

HMI Panel Instruction Manual
SmartWireless HMI Panel Instruction Manual
Rev. 1.0
Page 18 of 20
This will end the system diagnostics test and the display will revert back to the SYSTEM DIAGNOSTICS
menu.
5.3.6 Display Settings
The DISPLAY SETTINGS menu allows the user to customize the brightness, contrast and backlight
duration of the display. Upon entering this menu, the LCD will display:
DISPLAY SETTINGS
BRIGHTNESS: ###
BACKLIGHT OFF: ##:##
CONTRAST: ###
These values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt “→” to the desired function. A swipe over the ENTER marker will select the function
indicated by the arrow prompt “→” and the value can be changed by swiping over the markers of the up or
down arrows. Another swipe over the ENTER marker will save the selected value. Values for brightness
can range between 0 and 100 in increments of 10. Values for contrast can range between 30 and 100 in
increments of 10. Available values for the backlight timeout function are OFF, 10 seconds, 30 seconds and
1-5 minutes. The backlight timeout is the amount of time the user has before the LCD backlight will turn
off while in the Main Display due to inactivity.
5.3.7 About System
The ABOUT SYSTEM menu displays system information such as the HMI firmware version, the HMI
hardware version, the microcontroller firmware version and the RXT-300 firmware version and device
image. Upon entering this menu, the LCD will display:
DETCON INC
SMART WIRELESS HMI PANEL
VERSION #.##
Swipe the magnet over the marker of the down arrow to display the hardware information. Perform
another swipe to display the microcontroller information. Perform a final swipe to display the RXT-300
information. By swiping the magnet over the marker of the up arrow, the display will revert to the previous
screen.
6.0
Warranty
Detcon, Inc., as the manufacturer, warrants under intended normal use each new SmartWireless™ HMI
panel to be free from defects in material and workmanship for a period of one year from the date of
shipment to the original purchaser. Should the controller fail to perform in accordance with published
specifications within the warranty period, return to Detcon, Inc., for necessary repairs or replacement. All
warranties and service policies are FOB the Detcon facility located in The Woodlands, Texas.