0 installation (n7 enclosure), 1 mounting, 2 modbus & power connections – Detcon SW-HMI-32-N7 User Manual
Page 13: Installation (n7 enclosure), Mounting, Modbus & power connections, Figure 12 sw hmi panel n7 assembly dimensions

HMI Panel Instruction Manual
SmartWireless HMI Panel Instruction Manual
Rev. 1.0
Page 9 of 20
3.0
Installation (N7 Enclosure)
3.1 Mounting
The Model SW-HMI-32-N7 panel comes assembled with an RXT-300 transceiver and a Smart Battery
Pack enclosed in an aluminum condulet with a custom terminal board. This assembly is attached to a
custom mounting plate making installation simple and easy onto a rigid pipe or structure with the two 2 ½”
U-bolts provided (refer to Figure 12).
SmartWireless HMI Panel
RXT-300
Transceiver
If an Alarm reset switch is installed, the switch should
be mounted in the bottom port of the condulet.
If no reset switch is installed, install a
3
4
" NPT Plug.
Serial Number
Plate
www.detcon.com
Houston, Texas
SW HMI Mounting Plate
11"
22"
15.52"
25"
Term Board & Smart Battery
2
1
2
" U-Bolt
Mounting Holes
3.4"
Figure 12 SW HMI Panel N7 Assembly Dimensions
3.2 Modbus & Power Connections
Power to the SmartWireless™ HMI panel assembly in the N7 enclosure is provided by Detcon’s Smart
Battery Pack supplying +12VDC to the RXT-300 transceiver and the SW HMI panel. The Smart Battery
Pack plugs into the custom terminal board which resides inside the aluminum condulet. This terminal
board has separate plug-in connectors available for the transceiver and panel through which power and I/O
connections are made (refer to Figure 13 ). The term board and battery pack can be easily accessed by
removing the condulet lid.