beautypg.com

L1 l2 r y b – Star Water Systems Star 4in Sub Instr2&3-wire User Manual

Page 9

background image

16

Copyright © 2014 Star Water Systems. All rights reserved.

17

Copyright © 2014 Star Water Systems. All rights reserved.

ELECTRICAL HOOkUP FROM THE HOUSE TO PUMP AND PRESSURE TANk

2. Remove the cover from the control box and

mount it in an indoor location protected from

moisture.

(Fig. 2)

4. Attach the black, yellow and red wires to the

appropriate terminals marked “B”, “Y” and “R”.

(Fig. 4)

5. Connect the green ground wire from the pump

to the green ground screw in the lower right

corner of the control box.

(Fig. 5)

3. Thread the electrical wire from pump into the

right opening in the bottom of the control box

and tighten the electric wire strain relief securely.

(Fig. 3)

L1 L2

R

Y

B

Terminal

L2

Terminal

R

Terminal

Y

Terminal

B

Green

Ground

Screw

Terminal

L1

Green

Ground

Screw

2

L1 L2

R

Y

B

IL1176

L1 L2

R

Y

B

IL1175

4

5

L1 L2

R

Y

B

IL1174

3

ELECTRICAL HOOkUP FROM THE HOUSE TO PUMP AND PRESSURE TANk

L1 L2

R

Y

B

IL1177

6

L1 L2

R

Y

B

IL1178

L1 L2

R

Y

B

IL1179

7

L1 L2

R

Y

B

IL1180

8

9

9. Remove cover from pressure switch and screw

the switch into the 1/4 in. opening on the top of

the pipe tee.

(Fig. 9)

6. Thread the electrical wire from the pressure

switch into the left opening at the bottom of the

control box and tighten the electric wire strain

relief securely.

(Fig. 6)

7. Connect the two wires from the pressure switch

to the terminals in the control box marked L1 and

L2.

(Fig. 7)

8. Connect the green ground wire from the

pressure switch to the green ground screw in the

lower left corner of the control box and re-install

the control box cover.

(Fig. 8)