Warning, Clearance to combustibles – Hired-Hand Universal Ray Tube Heaters: AG2 Series Rev.10-08 User Manual

Page 5

background image

WARNING

!

!

Placement of explosive objects, flammable objects, liquids and vapors close to
the heater may result in explosion, fire, property damage, serious injury or death.
Do not store or use explosive objects, liquids or vapor in the vicinity of the heater.

Clearance to combustibles is defined as the minimum distance that must exist between the tube surface,
or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that must be
maintained from moving objects around the tube heater. When installing the tube heater system, clearances
to combustibles for the Series tube heater and configuration must be maintained.

Clearance to Combustibles

Model Number

Mounting

Angle*

Sides

Front

Behind

Top**

Below

AG2 (20, 30, 40) - (65, 75) [N, P]

9

9

6

60

45°

39

8

10

60

with 1 side shield

29

8

6

60

with 2 side shields

9

9

6

60

20 ft. from burner

7

7

6

30

AG2 (30, 40, 50) - 100 [N, P]

14

14

6

66

45°

39

8

10

66

with 1 side shield

29

8

6

66

with 2 side shields

16

16

6

66

20 ft. from burner

7

7

6

30

AG2 (40, 50) - 125 [N, P]

20

20

6

76

45°

58

8

10

76

with 1 side shield

42

8

6

76

with 2 side shields

20

20

6

76

20 ft. from burner

7

7

6

30

AG2 (40, 50, 60) - 150 [N, P]

24

24

6

81

45°

58

8

10

81

with 1 side shield

42

8

6

81

with 2 side shields

23

23

6

81

20 ft. from burner

11

11

6

44

5

1.0

Safety • Clearance to Combustibles

Chart 1.1 •

Clearance to Combustibles in Inches (see Figure 1.1 for Mounting Angles)

Figure 1.1

Mounting Angles

0° Mounting Angle

45° Mounting Angle

0° Mounting Angle

with 1 Side Shield

0° Mounting Angle

with 2 Side Shields

Side

Side

Below

Top

Front

Behind

Front

Behind

Side

Side

AG2

Series

* Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is greater.

** Maintain a 10 in. (0° mounting angle) or 12 in (1-45° mounting angle) clearance from ceilings constructed of tri-ply

plastic or plastic fogger lines.

Top

Top

Top

Below

Below

Below