beautypg.com

2) internal hf burst generator level, 3) and (4) impedance low and high limits, 5) back to previous menu – Nexo NUAR User Manual

Page 71: 6) selected channel

background image

MENU DESCRIPTION

If external pilot tone is used (from the audio program sent to the NXAMP on its analog or

digital inputs), be sure that the frequency selected here is as close as possible to the

frequency of the pilot tone.

(2) Internal HF burst generator level

The level of the internal HF burst generator can be adjusted here.

If the load monitoring function is not needed, or if external pilot tone is used, set the level

to OFF.

If the user wants to use the internal HF burst generator for impedance monitoring, then set

the level to the desired voltage between 0.5 and 5 volts. This voltage is intended at the

output of the NXAMP speakon connectors for the channel selected in zone 6, when all

settings are set to default position, with a FLAT setup, except the volume set to 0 dB

attenuation. The true output voltage can be slightly different depending on selected

speaker setup and user settings, but this does not affect the performance of the load

monitoring system.

Set the level to 1 volt is a good start, then adjust the output level to have a stable reading

of the impedance in the zone 7 of the display. Long speaker cable and high impedance

speaker(s) connected might need a higher output voltage. A too big output voltage can

lead to sub harmonic generation that can be audible at the speaker output.

(3) and (4) Impedance low and high limits

Once the measured impedance is display in the Zone 7, you can select low and high limits

that will trigger the fault report on the GPIO port of the NXAMP of on the Ethersound™

network.

To report the impedance fault on the GPIO port, set the GPIO to mode 5 (see above). To

report the impedance fault on the Ethersound™ network, dedicated hardware (like Auvitran

AVNF49-ES) or software should be used. Please contact us for further details on this.

These limits in zone 3 and 4 should be adjusted with care; External parameters such as

cable type and length, temperature, wind and output level can slightly change the

speaker’s impedance measurement.

Be sure to adjust these limits on site in real life conditions to prevent false triggering of the

impedance fault.

(5) Back to previous menu

Use the A button to go back to previous menu (“Options”).

(6) Selected Channel

Use the B button to select the channel currently affected by the settings of the zone 1, 2, 3

and 4.

PAGE 71 OF 140

This manual is related to the following products: