STEP 6 ELECTRICAL INSTALLATION
WARNINGS:
The electrical installation must be carried out in accordance with the
current national electrical regulations and installed by a competent
person.
In the interests of electrical safety a 30mA residual current device
(R.C.D.) should be installed in the supply circuit. This may be part of
a consumer unit or a separate unit.
The motor and wiring must not be exposed to water.
Before starting work on the electrical supply ensure power supply is
isolated.
The motor fitted to this pump is suitable for a 230/1/50Hz supply. It is thermally protected
by an integral auto resetting thermotrip for your safety and rated for the duty listed in the
technical specification section.
Electrical Connection
The motor is provided with a factory fitted supply cord. This must be permanently
connected to the fixed wiring of the mains supply. Means for disconnection must be
incorporated in the fixed wiring in accordance with the wiring rules.
A suitable method of connection would be via a double pole switched, fused connection
unit complying with BS 1363-4, protected with a fuse (see fuse section).
The connection unit should be mounted in an easily accessible position and should be
labelled if confusion is possible, to allow easy identification of the pump isolating switch.