- 14 -

5. The pressure vessel air pre-charge does not require routine maintenance. Should

ever the need arise for the vessel to have its air pre-charge checked or replenished, it

should be carried out as follows: -

a) Isolate pump electrically.

b) Isolate cold inlet water supply by closing the appropriate valve.

c) Release system water pressure by opening a system outlet (tap).

d) Check air pre-charge at Schrader valve (Fig. 2) using a tyre pressure gauge.

Pressure should be 140 kPa (1.4 bar or 20.3 psi).

e) Replenish air charge if required by injecting air into the vessel via the Schrader

valve using a car or bicycle pump, ensuring a system outlet valve (tap) remains

open during this procedure to allow the vessel to exhaust any excess water.

f) Close all system taps, open cold inlet isolating valve, turn on electrical power.

g) After maintenance is completed refer to commissioning section for instructions on

re-starting

pump.

Cleaners, Disinfectants and Descalents

On installations where chemical disinfectants or descalents are periodically

used, the compatibility of the chemical solution regarding the pump must be
considered.

Acid based descalents and aggressive cleaning agents must not come into

contact with the pump. The pump must be removed from the system prior to the
use of these products. The system should be flushed to remove all chemicals
before the pump is re-connected.

If in any doubt as to the suitability of the chemical solutions, please contact our

Pump Assist helpline.