beautypg.com

Stuart Turner 3.2 bar PS User Manual

Page 13

background image

- 13 -

4. Pre-Start

Check

Always ensure the static inlet and outlet heads above the pump do not exceed the

permitted maximum (see pump location section).

5. Starting

The

Pump

a) Ensure all outlets are closed, turn power supply ‘on’ - pump will start, pressurise

the system then stop.

b) Open and close all outlets in turn associated with the pump, (including w/c

systems) allowing water to flow from each outlet until all air is purged. As each

outlet is opened the vessel will discharge its stored water until pressure falls

when pump will start and satisfy demand.

After closing the outlet there will be a delay before the pump stops, which is

normal.

Any tap or control valve within the system when opened and closed will now

initiate this sequence of events. Providing this is the case the system is now

operating

correctly.

c) Carefully check pump and pipework for leaks whilst pump running and stationary

before leaving the installation unattended.

For Further Technical Support

Phone the Stuart Turner Pump Assist team on 0844 98 000 97. Our staff are trained to

help and advise you over the phone or arrange for a service engineer to call.

MAINTENANCE

WARNINGS:

Care should be taken to protect pump from frost and freezing,

particularly when located in a loft installation.

Pump Location

If possible site the pump in a location where in the unlikely event of a

water leak, any spillage is contained or routed to avoid electrics or

areas sensitive to water damage.

1. No routine maintenance is required but provision should be made

for easy access to the pump to allow for repairs due to normal wear

and

tear.

2. Disconnect electrical supply before working on pump.

3. Turn off water supplies to the pump and release pressure by opening water outlets

before attempting maintenance.

4. The inlet strainer incorporates a removable gauze filter which may require periodical

cleaning. The frequency of this operation is dependent upon installation conditions.

The strainer is located in the inlet pipework to the pump (see page 7). The gauze

filter is removed as follows:-

a) Isolate pump electrically.

b) Release all system pressure.

c) Isolate water supply.

d) Remove screwed hexagonal plug from strainer body (see page 7).

e) Remove and clean stainless steel gauze filter.

f) Reassemble gauze and secure plug tightly.

g) See commissioning section for instructions on re-starting pump.

This manual is related to the following products: