<5. MODBUS Communication >

5-5

IM 77J04J11-01E 1st Edition : 2006.08.25-00

03

Reads data from multiple D registers

Function

Reads the contents of a sequence of contiguous D registers by the specified number of D
registers, starting at a specified D register number.

The maximum number of D registers to be read at a time is 64.

For the format of response in the event of failure, see subsection 5.2.2.

Message (for normal operation)

Number of bytes in RTU mode

Number of bytes in ASCII mode

None

1

1

2

4

1

2

2

Error

Check

2

End of Message

Mark (CR+LF)

None

Element

Start of

Message Mark

(:)

Address

Number

(ADR)

Function

Code (03)

D-Register

Start Number

Number of

D Registers

2

4

2

2

Message (continued)

Response (for normal operation)

Response (continued)

Element

Start of

Message Mark

(:)

Address

Number

(ADR)

Function

Code (03)

Byte

Count

Contents of

D Register

Number of bytes in RTU mode

None

1

1

1

2

1

2

2

2

4

Number of bytes in ASCII mode

Contents of

D Register

Error

Check

End of Message

Mark (CR+LF)

None

2

2

2

2

4

• • •

• • •

• • •