2 function codes, 1 list of function codes – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual
Page 50

5-4
<5. MODBUS Communication >
IM 77J04J11-01E 1st Edition : 2006.08.25-00
5.2
Function Codes
5.2.1
List of Function Codes
Function codes are command words used by the higher-level device to obtain the D regis-
ter data of the M Series.
Table 5-2
List of Function Codes
Code Number
03
Reads data from multiple
registers.
Capable of reading data from a maximum of 64 successive
registers.
06
Writes data into a register.
Capable of writing data into one register.
Writes data into multiple
registers.
16
Capable of writing data into a maximum of 64 successive
registers.
Performs loop back test.
08
Used to check the connection for communication.
Function
Description
•
The write function codes will not write into read-only or disabled registers.
•
Broadcast addressing is possible with function codes 06 and 16 only. (Also in this
case, read-only or disabled registers will not be written into.)