Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual
Page 11

<1. Setup >
1-3
IM 77J04J11-01E 1st Edition : 2006.08.25-00
●
Address number (ADR)
Set the address number of the M Series itself. An address number of 1 to 99 can be as-
signed in any order. Note that the number of M Series that can be connected to a single
communication port is limited to 31.
Example of connecting four M Series to a higher-level device by setting address numbers
of 1, 5, 10 and 20
ADR=1
ADR=20
ADR=10
ADR=5
A maximum of 1200 m; up to 31 slave stations
PC
●
Baud rate (BPS)
Set the baud rate identical to that of the higher-level device to be connected. (Otherwise,
proper communication cannot be achieved.) The unit of the baud rate is kbps (kbits per
second).
●
Parity (PRI)
Set the handling of parity to be carried out when data is sent or received. Set the parity bit
state identical to that of the higher-level device to be connected.
●
Stop bit (STP)
Set the stop bit identical to that of the higher-level device to be connected.
●
Data length (DLN)
Set the data length identical to that of the higher-level device to be connected. (When
Ladder or MODBUS communication is selected in protocol selection, the data length is
fixed.)