08 performs a loop back test, Function, Message (for normal operation) – Yokogawa JUXTA VJ Series Limit Alarms User Manual

Page 47: Response (for normal operation), Example

background image

<5. MODBUS Communication >

5-7

IM 77J01J11-01E

3rd Edition : Oct. 15, 2007-00

08

Performs a loop back test.

Function

This function code is used to check the connection for communication.

For the format of responses in the event of failure, see subsection 5.2.2.

The element marked with * is "00" (fixed).

Any value can be selected to send data.

Message (for normal operation)

2

1

1

None

4

2

2

1

Number of bytes in RTU mode

Number of bytes in ASCII mode

2

4

Address

Number

(ADDRESS)

Start of

Message Mark

(:)

Element

Function

Code (08)

00*

0000

Send Data

(any)

050216E.EPS

Message (continued)

Error

Check

End of Message

Mark (CR+LF)

None

2

2

2

Response (for normal operation)

2

1

1

None

4

2

2

1

Number of bytes in RTU mode

Number of bytes in ASCII mode

2

4

Address

Number

(ADDRESS)

Start of

Message Mark

(:)

Element

Function

Code (08)

00

0000

Same as

send data

050217E.EPS

Response (continued)

Error

Check

End of Message

Mark (CR+LF)

None

2

2

2

Example:

Sending data "1234h" in hexadecimal to the VJ Series signal conditioner with communica-
tion address 1 to check connection for communication.

The following message sends "1234" (hexadecimal) to communication address 1 in the
ASCII mode.

[Message]

: 010800001234B1[CR][LF]

Start of message mark

When connection for communication is normal, the response whose configuration is the
same as that of the message is returned with respect to the above message.

[Response]

: 010800001234B1[CR][LF]