beautypg.com

3 response error codes – Yokogawa JUXTA VJ Series Limit Alarms User Manual

Page 18

background image

3-4

<3. PC Link Communication >

IM 77J01J11-01E

3.1.3

Response Error Codes

See Also

3.1.2, “Configuration of Response”, for the structure of response in the event of error.

The error codes (EC1) and detailed error codes (EC2) of responses are as follows.

Table 3-1 List of Error Codes EC1

02

Error code

Meaning

Cause(s)

• No command exists.
• Command not executable

03

• No register number exists.
• Invalid specification of bit register (I relay) when it is used on a word basis

04

• Any character other than 0 or 1 is used for bit setting.
• A value other than 0000 to FFFF has been specified in word specification.
• The position of a start for a data load is out of the address range.

05

• The specification of the number of bits, words, etc. is out of the range of

use.

• The number of data specified and that of parameters for registers and

others are not consistent.

06

• An attempt was made to execute monitoring without specifying the

monitor (BRS or WRS).

• An illegal parameter is set.

08

Parameter error

• The sum does not match the expected value.

42

43

Internal buffer overflow

Command error

Device specification error

Out of setpoint range

Out of data count range

Monitor error

Sum error

Character reception timeout

• A data value greater than the specified was received.

44

• The end-of-data or end-of-text character has not been received.

030229E.EPS

Table 3-2 List of Detailed Error Codes EC2

Detailed Error Code (EC2)

Device specification error

Out of setpoint range

Out of data count range

Parameter number where error occurred (HEX)
This is the sequence number of a parameter that first resulted in an error
when counted from the leading parameter.

e.g.:

Device name specification error

[STX]01010BRR02I0001,D0001[ETX][CR]

Parameter numbers 1 2 3

[STX]0101ER0303BRR[ETX][CR]

Error Code (EC1)

03

04

05

08

Parameter error

• An illegal parameter is set.

Meaning

030230E.EPS

For error codes other than those noted as EC1, there is no EC2 meaning.

3rd Edition : Oct. 15, 2007-00