Communications with daqlogger, Communications with daqlogger client package, Gatecontrol settings – Yokogawa DAQWORX User Manual
Page 40: Communications with daqlogger -9, Communications with daqlogger client package -9, Gatecontrol settings -9

3-9
IM WX1-07E
Funct
ons
1
2
3
Index
3.4
Notes When Performng Communcatons wth
Software on Other PCs
Communcatons wth DAQLOGGER
• When performing communications with DAQLOGGER, set the IP address of
the device with which DAQLOGGER will connect on the address of the PC that
GateCONTROL is operating, then execute automatic model determination.
• On DAQLOGGER, all devices connected to GateCONTROL (temperature controllers
and signal conditioners) are considered a single system. Therefore, the following
should be noted.
• DAQLOGGER’s automatic model determination determines only the lowest-
numbered device if multiple devices are connected to GateCONTROL (temperature
controllers and signal conditioners). For determination of the other devices, specify
the port number and system number (a number that is 1 less than the number
in the GateCONTROL’s Model Settings tab) in the DAQLOGGER settings, then
execute the automatic model determination function.
• When connecting all devices connected to GateCONTROL to DAQLOGGER
as one system, specify “No system number” in the address setting screen, then
execute automatic model determination.
Communcatons wth DAQLOGGER Clent Package
Check the port number (initial value is 50299) and system number set in GateCONTROL,
then reconnect. The logic behind the system numbers is the same as that for
DAQLOGGER.
GateCONTROL Settngs
Set the same serial and model settings as the connected device on GateCONTROL.