Setup items and default values – Yokogawa µR10000 User Manual
Page 51
51
IM 04P01B01-02E
Setup Items and Default Values
Setup Items in Setting Mode and Their Default Values
(Recorder version: 1.31)
The items with an asterisk are not displayed in the default condition. To display these
items, settings must be changed in Basic Setting mode.
Setup Item
Pen/Dot
Selectable Range or Selections
Default Value
Range > CH
-
01 to 06
01
Range > Mode
-
Volt/TC/RTD/1-5V/Scale/Delta/DI/SQRT/Skip
Volt
Range > Mode > Range
-
20mV/60mV/200mV/2V/6V/20V/50V/1-5V/
R/S/B/K/E/J/T/N/W/L/U/WRe/Pt/JPt/Level/Cont/
(Selections for /N1 and /N3 options)
2V
*Bias > CH
-
01 to 06
01
*Bias > Bias
-
On/Off
Off
*Bias > Bias
-
±10 % of the span of the measurable range or
the scaling span
-
Calibration (/CC1 option)
Calibration > CH
-
01 to 06
01
Calibration > Calibration
-
On/Off
Off
Calibration > datums
-
Within the range
-
Calibration > revise
-
Within the range
(correction point + correction value for revise value)
-
Calibration > Decision
-
Yes/No
Yes
Alarm > CH
-
01 to 06
01
Alarm > Level
-
1/2/3/4
1
Alarm > Alarm
-
On/Off
Off
Alarm > Type
-
H/L/h/l/R/r (*/T/t)
H
Alarm > Value
-
Depends on the alarm type.
-
Alarm > Relay
-
On/Off
Off
Alarm > Relay No.
-
I01 to I06
I01
Unit > CH
-
01 to 06
01
Unit > Unit
-
6 characters or less
Blank
Chart
Pen Model 82 types (pen model)
20 mm/h
Dot Model 1 to 1500 mm/h (dot model)
20 mm/h
Clock
-
Date/Time
-
Aux > Trend
Dot Model Auto/Fix
Auto
Aux > Zone > CH
-
01 to 06
01
Aux > Zone > Left, Right
-
Within the recording span range (mm)
Left: 0, Right: 100
*Aux > Partial > CH
-
01 to 06
01
*Aux > Partial > Partial
-
On/Off
Off
*Aux > Partial > Expand
-
1 to 99%
50
*Aux > Partial > Boundary
-
Within the recording span range
-
Aux > Print out > CH
-
01 to 06
01
Aux > Print out > Trend
Dot Model On/Off
On
Aux > Print out > Periodic
-
On/Off
On
Aux > Tag > CH
-
01 to 06
01
Aux > Tag > Tag
-
7 characters or less
1 to 6
Aux > Message > Message No.
-
1 to 5
1
Aux > Message > (Message)
-
16 characters or less
Blank
Aux > Chart2
Pen Model 82 types (pen model)
20 mm/h
Dot Model 1 to 1500 mm/h (dot model)
20 mm/h
*Aux > Moving_AVE > CH
Dot Model 01 to 06
01
*Aux > Moving_AVE > No. of samples
Dot Model Off, 2 to 16
Off
*Aux > Filter > CH
Pen Model 01 to 06
01
*Aux > Filter > Resp. Time
Pen Model 2s/5s/10s
Off
*Aux > Alm delay T > CH
-
01 to 06
01
*Aux > Alm delay T > Duration
-
0 to 3600s
10s
Aux > Brightness > Display
-
1/2/3/4/5/6/7/8
4
Aux > Brightness > Light
-
1/2/3/4
2