Setup example (1) of thermocouple input – Yokogawa µR10000 User Manual
Page 33
33
IM 04P01B01-02E
Setting the Input Range and Alarm on Measurement
Channels
Setup Example (1) of Thermocouple Input
Set channel 02 to thermocouple type K and measure temperatures in the range –50.0 to
450.0°C. The measurable range for thermocouple type K is –200.0 to 1370.0°C.
The measured values in the range of –50.0 to 450.0°C are recorded in a width of 100 mm
on the chart paper. This recording range is called a recording span, and the leftmost and
rightmost values of the recording span are called span left and span right, respectively.
–200.0°C
1370.0°C
Measurable range of thermocouple type K
–50.0°C
450.0°C
(Span left)
100 mm
(Span right)
Chart paper
Entering Setting Mode
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
Selecting the Range
2.
Press the key with
Range shown on the screen.
Set=Range
Input range and
Displays a description of the setup item.
Selecting the Channel Range
3.
Press the
key to set the first channel to
02 and then press the key.
First channel Last channel
CH=02-02
First channel 01-
Displays the selectable range of channels.
4.
Likewise, set the last channel to
02 and then press the key.
Selecting the Input Type
5.
Press the
key to select
TC and then press the key (see “Explanation” on
page 38).
Mode=TC
Thermocouple
6.
Press the
key to select
K and then press the key.
Range=K
R,S,B,K,E,J,T,N
Displays the thermocouple type.
Setting Span Left
7.
Set Span_L to
–50.0 and press the key.
Press the
key to select the desired digit. Press the
key to select the value.
Span_L= -50.0
-200.0/ 1370.0°C
Displays the measurable range of
thermocouple type K.
* When the key or key is pressed while holding down the
SHIFT key, the operation is reversed as
when the respective key is pressed by itself.