10.2 Intrinsically safe ATEX certified components (/KS1)

10.2.1 Technical data

Data of electronic transmitter type -E, -H and -J :
The electronic transmitter is an intrinsically safe device. This device is certified for hazardous areas of zone 1 (cat-
egory 2) und zone 2 (category 3). It is not homologated for zone 0 (category 1). The classifications in brackets are
given according to EU-Regulation 94/9/EG (ATEX).

EC-Type Examination Certificate Nr.: PTB 12ATEX2003
Applicable standards:

EN 60079-0: 2009

EN 60079-11: 2007

Identification in accordance with regulation 94/9/EG (ATEX) :

II 2 G

Type of protection

: Intrinsically safe Ex ia IIC T6 Gb

Ambient temperature

: -40°C ... +70°C

Safety relevant maximum values:
Maximum voltage

: U

i

= 30 V

Maximum current (IIC)

: I

i

= 101 mA

Maximum power

: P

i

= 1.4 W

Inner inductance

: L

i

= 0.15 mH

Inner capacity

: C

i

= 4.16nF

Data of electronic transmitter type -G :
See IM 01R01B02-01E-E.

Data of limit switches :
The following table shows the maximum safety parameters for intrinsic safe limit switches according the certificates
PTB 99 ATEX 2219X (Standard) and PTB 99 ATEX 2049X (Fail Safe).
Table 10.1

Standard /K1 ... /K3

Ex ia IIC T6

Fail Safe /K6 .../K10

Ex ia IIC T6

Type 2

Type 3

Type 2

Type 3

Ui [V]

16

16

16

16

Ii [mA]

25

52

25

52

Pi [mW]

64

169

64

169

Ci [nF]

150

150

30

30

Li [µH]

150

150

100

100

max. ambient temp. [°C] for T6

49

28

49

28

max. ambient temp. [°C] for T5

61

40

61

40

max. ambient temp. [°C] for T4 - T1

89

68

89

68

The limit switches are also dust approved.
EC-Type Examination Certificate No.: ZELM 02 ATEX 0128X
Identification in accordance with regulation 94/9/EG (ATEX) :

II 1 D

Type of protection

: Ex iaD 20

Maximum surface temperature

: 108°C.

The dust explosion proof for the limit switches is only available if ordered without electronic transmitter (only with
housing type "T").