An adjusting step corresponds to 20 µA. The complete adjusting range is ± 0.62 mA (31 steps). If the
adjusting range does not suffice, change to display F32 or F33 by pressing ENTER when display shows F32
31 or F33 31, press ENTER again and continue adjusting at F32 00 or F33 00.
3 wire connection:
At this the ranges 0-20 mA and 4-20 mA are possible. At a switch over between the two ranges with F31 the
current output is automatically adjusted at equipment as of firmware version 1.4 . (s.F 61). A perhaps
necessary fine adjustment can be carried out with F32 or F33.
2 wire connection:
At this only the range of 4-20 mA is meaningful. The range of 0-20 mA is not closed however. At the change
to 0-20 mA with F31 the equipment assumes a remodelling on 3 wire connection and the current output is
adjusted according to this. A perhaps necessary fine adjustment can be carried out with F32 or F33.

WARNING

Since YOKOGAWA doesn’t have any influence on the custom-designed connection the current output is not
automatically adapted, if the connection is changed from 2 wire to 3 wire or vice versa .This must be manually
carried out with the functions F32 and F33.

Preset values :

Connection

Current range

2- wire

3-wire

0 - 20 mA

---------

I

0

= 0 mA

I

20

= 20 mA

4 - 20 mA

I

4

= 0.4 mA + 3.6 mA

I

20

= 16.4 mA + 3.6 mA

I

0

= 4 mA

I

20

= 20 mA

Note

Do not use F31

Use F31 for changing

6.2.7 Pulse output (F34) (Option /CP)

With the function F34 the optional pulse output can be activated and adjusted.

Description

Selection

Key

Indication

Change to setting mode

Enter

Display mode
F1-

Setting mode

2 x →

Enter

3 x →

F3-
F31
F34

Selection

or

or

Activation

Resolution last digit

Resolution last but one digit

Enter
Enter

Enter

2 x →

Enter

F34 -1
F34
F34 -2
F34
F34 -3
F34

Back to display mode

F3-
Display mode