<5. Parameter Summary>
5-3
IM 01C25T03-01E
No. Parameter name
Item
*
1
R/W
Content
Default value
Applicable
model
U
pl
oa
d
da
ta
F
P
L
G
ALARM SET
Alarm setting
G10 P AL MODE
Alert mode
W INHIBIT, HI. AL DETECT, LO.
AL DETECT, or HI/LO. AL
DETECT
INHIBIT
—
G11 P HI. AL VAL
High side alert value
W -32000 to 32000, unit
specified in C20
100.000 kPa
—
G12 P LO. AL VAL
Low side alert value
W -32000 to 32000, unit
specified in C20
-100.000 kPa
—
G20 SP AL MODE
Static pressure alert mode
W INHIBIT, HI. AL DETECT, LO.
AL DETECT, or HI/LO. AL
DETECT
INHIBIT
—
—
G21 SP HI. AL VAL
High side alert value of SP*
2
W -32000 to 32000, unit
specified in D30
—
—
G22 SP LO. AL VAL
Low side alert value of SP
W -32000 to 32000, unit
specified in D30
0.00000 MPa
—
—
G30 T AL MODE
Temperature alert mode
W INHIBIT, HI. AL DETECT, LO.
AL DETECT, or HI/LO. AL
DETECT
INHIBIT
—
G31 T HI. AL VAL
High side alert value of
temperature
W -50 to 130
120 degC
—
G32 T LO. AL VAL
Low side alert value of
temperature
W -50 to 130
-40 degC
—
G50 AUTO RECOVER Auto-recover from sensor error
W OFF or ON
ON
—
G60 SELF CHECK
Self-diagnostics
R
See A60
—
H
AUTO SET
Automatic setup
H10 AUTO P LRV
Lower range value auto setup
W -32000 to 32000, unit
specified in C20
As specified
—
H11 AUTO P URV
Upper range value auto setup
W -32000 to 32000, unit
specified in C20
As specified
—
H20 AUTO SP LRV
SP lower range value auto
setup
W -32000 to 32000, unit
specified in D30
0.00000 MPa
—
—
H21 AUTO SP URV
SP upper range value auto
setup*
2
W -32000 to 32000, unit
specified in D30
—
—
H60 SELF CHECK
Self-diagnostics
R
See A60
—
I
DISP SET
Display setting
I10
DISP OUT1
LCD output 1
W PRES, PRES %, ENGR.
PRES, SP, or SP %
PRES %
I11
DISP OUT2
LCD output 2
W PRES, PRES %, ENGR.
PRES, SP, SP %, or ---
---
I12
DISP OUT3
LCD output 3
W See I11
---
I13
DISP OUT4
LCD output 4
W See I11
---
I20
P DISP MODE
% display mode
W LINEAR or SQUARE ROOT
LINEAR
I21
PRES % RESO
% display resolution
W NORMAL or HIGH
RESOLUTION
NORMAL
I30
ENGR. UNIT
User set engineering unit
W 8 alphanumeric characters
I31
EASY EU SET
Engineering unit select
W
—
I32
ENGR. EXP
Exponents
W ---, Ч10, Ч100, Ч1000
---
I33
ENGR. LRV
User set lower range limit
W -32000 to 32000, unit
specified in I30
0.00
I34
ENGR. URV
User set upper range limit
W -32000 to 32000, unit
specified in I30
100.00
I35
ENGR. POINT
Decimal place of user set
W 0 to 4
1
I40
BAR INDICATR
Bar indicator
W OFF or ON
ON
I41
POWER ON INF
Display when powering on
W OFF or ON
ON
—
I60
SELF CHECK
Self-diagnostics
R
See A60
—
*1: R/W: R = Read only, W = Read & Write
*2:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.