21) adjustment information and user memo fields, 3 displaying data using the bt200, 1 displaying measured data – Yokogawa EJA440E User Manual
Page 28: Displaying data using the bt200 -20 3.3.1, Displaying measured data -20
<3. Operation>
3-20
IM 01C25T03-01E
Transmitter
L
h
0
H
(+)
● EJX118A/EJA118E
F0353.ai
h
h
L
L
H
Transmitter
Transmitter
0
(+)
(–)
● EJX438A/EJA438E
Note: When the transmitter is positioned lower than the
diaphragm seal part, the value of “h” must have a
negative sign (–).
Enter “–0.149.”
Press the key twice
to enter the setting.
F0354.ai
ESC
SET
E11:TEMP ZERO
0.000 %/degC
- 00.149
CLR
OK
SET
E11:TEMP ZERO
-0.149 %/degC
NO
FEED
K=−(+3)Ч0.00745ч15Ч100=−0.149
Press the (OK) key.
• Example: Enter K value obtained from the
equation (a). A value having up to 3
decimal places may be specified.
When h=+3 m, Fill fluid code A, span=15 kPa,
Note 1: The function is performed using a built-in temperature
sensor in the transmitter body. The temperature
deviation between the transmitter body and capillaries
should be minimized to achieve optimal performance
of the function.
Note 2: When the span changes, reenter the newly obtained
value of K to E11: TEMP ZERO.
Table A. Constant value [B] of fill fluid
Fill fluid
code
A, C,
1, 2, 4
B
D
E
C
on
st
an
t v
al
ue
[B
]
mmH
2
O 0.76
0.87
1.45
0.75
kgf/cm
2
0.000076 0.000087 0.000145 0.000075
kPa
0.00745
0.00853
0.01422
0.00736
mBar
0.07453
0.08532
0.14220
0.07355
atm
0.000074 0.000084 0.000140 0.000073
inH
2
O
0.02992
0.03425
0.05709
0.02953
psi
0.00108
0.00124
0.00206
0.00167
mmHg
0.05592
0.06401
0.10669
0.05518
Note 3: Select the unit of constant value of [B] from the actual
unit used for the transmitter in operation.
(21) Adjustment Information and User
Memo Fields
(J50: ADJ WHO, J51: ADJ DATE, J52:
ADJ LOC, J53: ADJ DESC, M17 to M19:
MEMO1 to MEMO3)
This feature provides four fields for instrument
adjustment information at maintenance: inspection
date, inspector, location, and description. Also three
user memo fields are provided, each holding up to
16 alphanumeric characters.
• Example: Save an inspection date of October
21, 2003.
DATA
DIAG
PRNT
ESC
SET
J51:ADJ DATE
MM-DD-YYYY
10-21-2003
ESC
CODE CAPS
CLR
PARAM
J50:ADJ WHO
J51:ADJ DATE
J52:ADJ LOC
Set “10-21-2003” in the order of
month, day, and year.
Press the key twice to
enter the setting.
F0355.ai
3.3 Displaying Data Using the
BT200
3.3.1 Displaying Measured Data
The BT200 can be used to display measured data.
The measured data is updated automatically
every seven seconds. In addition, the display can
be updated to the present data value at any time
by pressing the
(DATA) key. For parameters
associated with the display of measured data, see
chapter 5 Parameter Summary.
• Example: Display output.
DATA
DIAG
PRNT
ESC
HOME
SET
ADJ
ESC
F0356.ai
Data is updated automatically
at 7-second intervals.
Display “A10: OUTPUT.”
communi
PARAM
A10:OUTPUT
0.0 %
A11:PRES
0.0000 kPa
A15:OUTPUT mA
4.000 mA
PARAM
A10:OUTPUT
0.0 %
A11:PRES
0.0000 kPa
A15:OUTPUT mA
4.000 mA
MENU
A:DISPLAY
B:SENSOR TYPE
C:BASIC SETUP
D:AUX SET1
E:AUX SET2
G:ALARM SET