Parameter summary, Parameter summary -1 – Yokogawa EJA440E User Manual
Page 33
<5. Parameter Summary>
5-1
IM 01C25T03-01E
5. Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters
P: Absolute and gauge pressure transmitters
L: Flange mounted differential pressure transmitters
No. Parameter name
Item
*
1
R/W
Content
Default value
Applicable
model
U
pl
oa
d
da
ta
F
P
L
01
MODEL
Model
R
EJX (for EJX series)
EJA (for EJA series)
—
02
TAG No.
Tag number
R
As specified
—
03
SELF CHECK
Self-diagnostics
R
GOOD
—
A
DISPLAY
Measured data display
A10 OUTPUT
Output (in %)
R
-2.5 to 110%
—
A11 PRES
Measured pressure after zero
adjustment
R
Unit specified in C20
—
A15 OUTPUT mA
Output current
R
3.600 to 21.600 mA
—
A16 ENGR. OUTPUT
User scaled value
R
Unit specified in I30
—
A17 ENGR. EXP
Exponents
R
Unit specified in I32
—
A20 SP %
Static pressure (in %)
R
-10 to 110%
—
—
A21 SP
Static pressure after zero
adjustment
R
Unit specified in D30
—
—
A30 CAPSULE TEMP
Capsule temperature
R
Unit specified in D40
—
A60 SELF CHECK
Self-diagnostics
R
Refer to Table 4.1 Alarm
Message Summary
—
B
SENSOR TYPE
Sensor type
B10 MODEL
Model and capsule type
R
Model and capsule type
—
B11 STYLE NO.
Style number
R
Style number of product
—
B20 PRES LRL
Lower range limit
R
Unit specified in C20
—
B21 PRES URL
Upper range limit
R
Unit specified in C20
—
B22 P MIN SPAN
Minimum span
R
Unit specified in C20
—
B30 SP LRL
Lower range limit for static
pressure
R
Unit specified in D30
—
—
B31 SP URL
Upper range limit for static
pressure
R
Unit specified in D30
—
—
B32 SP MIN SPAN
Minimum span for static
pressure
R
Unit specified in D30
—
—
B60 SELF CHECK
Self-diagnostics
R
See A60
—
C
BASIC SETUP
Setting data
C10 TAG NO.
Tag number
W 16 alphanumeric characters
As specified
C20 PRES UNIT
Measurement range unit
W mmH
2
O, mmAq, mmWG,
mmHg, Torr, kPa, MPa, mbar,
bar, gf/cm
2
, kgf/cm
2
, inH
2
O,
inHg, ftH
2
O, psi, atm, Pa, hPa
kPa
C21 PRES LRV
Lower range value
W -32000 to 32000 within
measurement range
As specified
C22 PRES URV
Upper range value
W -32000 to 32000 within
measurement range
As specified
C23 PRES POINT
Decimal place
W 0 to 4
2
C30 AMP DAMPING
Damping time constant at
amplifier
W 0.50(0.00) to 100.00 seconds,
see D50
2.00 seconds or
as specified
C40 OUTPUT MODE
Output mode
W LINEAR or SUQARE ROOT
LINEAR or as
specified
C60 SELF CHECK
Self-diagnostics
R
See A60
—
*1: R/W: R = Read only, W = Read & Write
*2:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.