Appendix, Specifications – Watlow series l rev g - 02-12-08.pdf User Manual
Page 21

Wa t l o w S e r i e s N 7
■
2 1
■
A p p e n d i x
Appendix
A
Specifications
Controller
•
Up to four sensor inputs, eight switched dc outputs, eight dc
inputs, two process outputs
•
Battery backed, real-time clock
•
One non-isolated slave communications channel
•
One non-isolated master communications channel
•
Optional ethernet communications module
•
Optional high-voltage output module
Operator Interface
•
Four-character, 0.56-inch, seven-segment display
•
Eight-character, 0.2 inch, alphanumeric display
•
Overlay interface supports up to 32 keys and LED indicator
lights
Overlay interface
•
Switch closed input < 100
Ω
•
Switch open input > 100 k
Ω
•
LED current limiting resistor: 200
Ω
•
LED supply voltage: 5V
Operating Environment
•
0 to 80°C (32 to 176°F) @ 0 to 90% RH, non-condensing
Standard Conditions For Specifications
•
Ambient temperature 25°C (77°F) ±3°C, 24VÅ (ac), 50 to 60 Hz
Configured Sensor Inputs
•
Update rate: 5Hz
Thermocouple
•
Multiple channel applications require at least one ungrounded
thermocouple.
•
Input current: 0.5 nA
•
Maximum source resistance: 20
Ω
•
Accuracy: ± 1.1°C (2°F)
•
Drift: ± 0.10°C/°C (± 0.10°F/°F)
•
Input ranges:
Type J: -46 to 316°C (-50 to 600°F)
Type K: -46 to 316°C (-50 to 600°F)
RTD
•
2- or 3-wire platinum
•
DIN curve (.00385 curve)
•
700 µA maximum excitation current
•
Accuracy: ± 1.1°C (2°F)
•
Drift: ± 0.10°C/°C (± 0.10°F°/F)
•
Range: -46 to 316°C (-50 to 600°F)
Voltage
•
Input impedance 60 k
Ω
•
Input range: 0 to 12V
•
Accuracy: ± 25 mV
•
Drift: ± 5mV/F
Current
•
Input impedance 100
Ω
•
Input range: 0 to 22mA
•
Accuracy: ± 40 µA
•
Drift: ± 5 µA/F
Event Input
•
Input high: 3 to 30V or >10 k
Ω
•
Input low: -0.5 to 0.5V or < 250
Ω
Outputs
Switched DC Outputs
•
5V at 30mA maximum
Voltage Output
•
Range: 0 to 12V at 20 mA maximum
•
Minimum: load impedance 500
Ω
•
Accuracy: ± 100mV
•
Drift: ± 2.1mV/F
Current Output
•
Range 0 to 22mA at 20V maximum
•
Maximum load impedance 1,000
Ω
•
Accuracy: ± 100µA
•
Drift: ± 4.3µA/F
Agency
•
UL 60730, c-UL File E43684
•
EU LV Directive 72/23/EEC EN 60730
•
EU EMC Directive 89/336/EEC
emissions
immunity
•
NSF Option, File 49660-0003-000
•
NAFEM Communications/Evaluate proper listing
•
CSA standard E60730-2-9
Power/Line Voltage
•
24 VÅ (ac) power input (20.4 to 26.4Å (ac)), Class 2 power
source required
•
47 to 63 Hz
•
15VA maximum
•
Program retention upon power failure via non-volatile memory
•
Battery/real time clock option: six-year lithium battery, pro-
vides power upon backup power failure, operation resumption
after power recovery, ability to display time.
Audible Alarm
•
Internal audible alarm, 85 dB @ 10cm @ 2 KHz. Output fre-
quencies supported: 250, 500, 1,000, 2,000, 4,000 Hz.
Storage Temperature
•
-40 to 80°C (-40 to 176°F)
Optional High-Voltage Board
•
Optional high-voltage board will have six outputs, either solid-
state relay, electromechanical relay or no-arc relay
Relay Specification:
Contact type: normally open
Maximum operating current: 8 A
Maximum operating voltage: 250VÅ (ac)
Pilot duty: 250 VA