beautypg.com

Appendix, Specifications – Watlow series l rev g - 02-12-08.pdf User Manual

Page 21

background image

Wa t l o w S e r i e s N 7

2 1

A p p e n d i x

Appendix

A

Specifications

Controller

Up to four sensor inputs, eight switched dc outputs, eight dc
inputs, two process outputs

Battery backed, real-time clock

One non-isolated slave communications channel

One non-isolated master communications channel

Optional ethernet communications module

Optional high-voltage output module

Operator Interface

Four-character, 0.56-inch, seven-segment display

Eight-character, 0.2 inch, alphanumeric display

Overlay interface supports up to 32 keys and LED indicator
lights

Overlay interface

Switch closed input < 100

Switch open input > 100 k

LED current limiting resistor: 200

LED supply voltage: 5V

Operating Environment

0 to 80°C (32 to 176°F) @ 0 to 90% RH, non-condensing

Standard Conditions For Specifications

Ambient temperature 25°C (77°F) ±3°C, 24VÅ (ac), 50 to 60 Hz

Configured Sensor Inputs

Update rate: 5Hz

Thermocouple

Multiple channel applications require at least one ungrounded
thermocouple.

Input current: 0.5 nA

Maximum source resistance: 20

Accuracy: ± 1.1°C (2°F)

Drift: ± 0.10°C/°C (± 0.10°F/°F)

Input ranges:

Type J: -46 to 316°C (-50 to 600°F)
Type K: -46 to 316°C (-50 to 600°F)

RTD

2- or 3-wire platinum

DIN curve (.00385 curve)

700 µA maximum excitation current

Accuracy: ± 1.1°C (2°F)

Drift: ± 0.10°C/°C (± 0.10°F°/F)

Range: -46 to 316°C (-50 to 600°F)

Voltage

Input impedance 60 k

Input range: 0 to 12V

Accuracy: ± 25 mV

Drift: ± 5mV/F

Current

Input impedance 100

Input range: 0 to 22mA

Accuracy: ± 40 µA

Drift: ± 5 µA/F

Event Input

Input high: 3 to 30V or >10 k

Input low: -0.5 to 0.5V or < 250

Outputs

Switched DC Outputs

5V at 30mA maximum

Voltage Output

Range: 0 to 12V at 20 mA maximum

Minimum: load impedance 500

Accuracy: ± 100mV

Drift: ± 2.1mV/F

Current Output

Range 0 to 22mA at 20V maximum

Maximum load impedance 1,000

Accuracy: ± 100µA

Drift: ± 4.3µA/F

Agency

UL 60730, c-UL File E43684

EU LV Directive 72/23/EEC EN 60730

EU EMC Directive 89/336/EEC

emissions
immunity

NSF Option, File 49660-0003-000

NAFEM Communications/Evaluate proper listing

CSA standard E60730-2-9

Power/Line Voltage

24 VÅ (ac) power input (20.4 to 26.4Å (ac)), Class 2 power
source required

47 to 63 Hz

15VA maximum

Program retention upon power failure via non-volatile memory

Battery/real time clock option: six-year lithium battery, pro-
vides power upon backup power failure, operation resumption
after power recovery, ability to display time.

Audible Alarm

Internal audible alarm, 85 dB @ 10cm @ 2 KHz. Output fre-
quencies supported: 250, 500, 1,000, 2,000, 4,000 Hz.

Storage Temperature

-40 to 80°C (-40 to 176°F)

Optional High-Voltage Board

Optional high-voltage board will have six outputs, either solid-
state relay, electromechanical relay or no-arc relay

Relay Specification:

Contact type: normally open
Maximum operating current: 8 A
Maximum operating voltage: 250VÅ (ac)
Pilot duty: 250 VA