Maple Systems MAP460D User Manual
Page 12

IMPORTANT: When panel mounting the MAP460D, do not catch the display
connector on the panel cutout. The display is exposed while panel mounting and
extra care should be taken. The display can be damaged if the display cable
connector, which protrudes from the panel cutout, is touching the panel when
tightened. To avoid damage, place the MAP460D gently onto the panel while
monitoring for this condition.
Pedestal/Pendent Mount
The OIT is installed onto a pedestal/pendent by removing the four rubber feet from
the rear cover of the OIT, then attaching the OIT to a mounting plate using the four
pre-tapped holes in the rear cover. The OIT enclosure and cable strain relief provide
the environmental seal to NEMA 4 and NEMA 12 standards.
Figure 9 shows the minimum dimensions of the pedestal/pendant mounting plate.
The area on the pedestal/pendant mounting plate around the mounting holes (where
the heads of the screws make contact) should have any existing paint or plating
removed to allow for a good chassis ground connection. The mounting screws are
installed using external tooth star washers to ensure a positive ground connection.
12
MAP460D
1010-0093, REV 03
Four #6-32UNC mounting
screws secure OIT to pedestal
Four #6 external tooth
star lockwashers provide
chassis ground
Figure 8 MAP460D Pedestal Mounting