RLM Power Requirements
The RLM must be powered from a dedicated 115 VAC
single circuit breaker, with no other devices connected
to wire or breaker. Do not use a switched neutral
breaker. The neutral must come directly from the
neutral bus in the electric supply panel. No other
neutral circuits may be connected to this wire.
The electric supply system earth bond must connect to
a driven ground rod or other earth bonding systems that
comply with the National Electrical Code, Article 250.
Failure to comply with these requirements
will void warranty.
System Installation
RLM General Installation
Read entire installation manual before attempting to install the system.
Note warnings on previous page.
RLM (Mechanical)
1.
A junction box with a single receptacle outlet must be provided.
See RLM Power Requirements listed below.
2.
Securely mount the RLM main box in a nonhazardous location
according to the suggested layout in the Tank Monitor Installation
instructions.