Operating procedures dmom-200 – Vanguard DMOM-200 User Manual
Page 18
Operating Procedures
DMOM-200™
13
5.5 Enter ID Procedure
This procedure allows the user to enter the
equipment identification to the test record.
Table 5.0
Run Setup Procedure (test-record, site, and equipment identification)
STEP
ACTION
DMOM-200
DISPLAY
5-1
Press key # 2 (SETUP MENU) on START
MENU to go to Setup menu (shown at
right).
5-2
On SETUP MENU, press #1 key (ENTER
ID) to begin identification entry (begins
with “COMPANY” display).
Note: Other setup options go to the
following procedural tables:
1. Review Record procedure in Table 6.0
2. Restore Record Procedure in Table 7.0
3. NEXT PAGE procedures.
5-3
Enter utility COMPANY name using
alpha/ numeric keypad. When the
COMPANY name is keyed in, press
ENTER to load keyed data and go to
STATION identification display.
5-4
Enter utility STATION name using alpha/
numeric keypad. When STATION name
is keyed in, press ENTER to load keyed
data and go to CIRCUIT identification
display.
5-5
Enter utility CIRCUIT name using alpha/
numeric keypad. When CIRCUIT name is
keyed in, press ENTER to load keyed data
and go to MANUFACTURER
identification display.
5-6
Enter tested item’s MANUFACTURER
name using alpha/numeric keys. When
the manufacturer’s name is keyed in, press
ENTER to load keyed data and go to
MODEL identification display.
1. ENTER ID
2. REVIEW RECORD
3. RESTORE RECORD
4. NEXT PAGE
COMPANY:
STATION:
CIRCUIT:
MANUFACTURER:
MODEL: