beautypg.com

Wiring nacs and idcs for class a – System Sensor PDRP-2001 User Manual

Page 30

background image

30

PDRP-2001 Series Manual — P/N 53043:E1 2/28/2011

Installation

Installation of Optional Modules

Wiring NACs and IDCs for Class A

Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit
board and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits using
TB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will be
identical when using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity when
connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return
for the positive side of a device and the B- and A- terminals must comprise the feed and return for
the negative side of a device. To configure any of the zones for Class B when the CAC-5X is
installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line
Resistor after the last device on the circuit. Do not wire to the corresponding A+ and A- terminals
on the CAC-5X module.

Figure 2.12 Wiring NACs and IDCs for Class A Operation

CAC-5X Class A Converter Module

FACP Main

Circuit Board

Class B (Style B) IDC - 4.7 K

½ watt ELR resistor

P/N:71252 (supervised and power-limited)

Dummy load all unused
circuits - 4.7 K

½ watt ELR resistor
(P/N: 71245)

Polarized

Bell

Circuit polarities
shown in alarm
condition

Class A (Style Z) NAC

(supervised and power-limited)

Class A (Style D) IDC
(supervised and power-limited)

Polarized

Strobe

Polarized

Horn

Smoke

Smoke

Pull Station

Pull Station

Heat

Heat

m

s10

udcl

assa.cd

r

B+ B-

B+ B-

A+ A- A+ A-

A+ A- A+ A- A+ A- A+ A- A+ A-

B+ B- B+ B- B+ B- B+ B- B+ B-